RCD, GFCI, RCBO and AFCI: How Protective Devices Keep You Safe

A modern panel can hold four different kinds of protective device. Each one watches for a different danger, and knowing which does what explains why none of them can replace the others.

Reviewed by Himanshu Amdavadi on . Facts, figures and calculations checked against the sources listed below.

Blueprint drawing of a toroidal current transformer with two conductors passing through it in opposite directions and a teal sensing coil connected to a trip unit.

Quick answer

A circuit breaker protects the cable from overload and short circuits. An RCD (UK/IEC) or GFCI (North America) protects people by tripping when current leaks to earth: at 30 mA for the RCDs used for personal protection, and 4–6 mA for Class A GFCIs. An RCBO combines an RCD and a breaker in one device. An AFCI (US) or AFDD (UK) detects arcing that could start a fire.

Key takeaways

  • Breakers and fuses protect wiring; they trip far too late to protect a person from shock.
  • RCDs and GFCIs compare the current going out with the current coming back.
  • They can’t detect a shock between live and neutral, so they add to, not replace, other protection.
  • Arc-fault devices target fire risk from damaged cords and loose connections.
In this article (6 sections)

A few tens of milliamps through the body can be fatal. A cable, on the other hand, can carry many amps safely. Protective devices exist because no single device can watch for both kinds of danger, plus the separate risk of fire from arcing.

Four devices, four jobs

Device Protects against Typical trip level Common names
Circuit breaker or fuse Overload and short circuit (cable damage, fire) Rated current, e.g. 15, 16, 20 or 32 A: trips on sustained overload above it, or instantly on a short circuit MCB, breaker, fuse
Residual-current device Electric shock from current leaking to earth 30 mA (RCD) or 4–6 mA (Class A GFCI) RCD, RCCB (UK); GFCI, GFI (US)
Combined device Both of the above, per circuit Rated current plus 30 mA (RCBO) or about 5 mA (Class A GFCI breaker) RCBO (UK); GFCI circuit breaker (US)
Arc-fault device Fire from series or parallel arcing Arc signature, not a current level AFCI (US); AFDD (UK)

Circuit breakers: protecting the wiring

A breaker has two trip mechanisms. A thermal element responds to sustained overload that would slowly overheat the cable. A magnetic element trips almost instantly on a short circuit. Fuses do the same job by melting.

Both are sized to protect the cable. A 16 A breaker will happily let 100 mA flow forever, and 100 mA through a person’s chest can be deadly. That is the gap residual-current devices fill.

RCDs and GFCIs: protecting people

In a healthy circuit, every amp that goes out on the live conductor comes back on the neutral. A residual-current device passes both conductors through a small ring-shaped transformer (a toroid). As long as the two currents are equal, their magnetic fields cancel.

If some current leaks to earth, perhaps through a damaged appliance or a person, the currents no longer balance. The difference induces a signal in a sensing coil, and the device trips quickly: a general-type RCD within 300 milliseconds at its rated 30 mA, and faster at higher leakage. A GFCI follows a curve too, tripping in about 25 milliseconds at 250 mA or more and taking up to a few seconds close to its 6 mA threshold.

  • GFCIs that protect people in North American homes are Class A devices: they trip at a ground-fault current of 6 mA or more and do not trip below 4 mA.
  • RCDs used for personal protection in the UK and IEC countries are rated 30 mA. BS 7671 requires this “additional protection” for socket-outlets rated up to 32 A and for mobile equipment up to 32 A used outdoors, among other circuits. The only exception is for socket-outlets in locations not used by ordinary people or children, where a documented risk assessment by a skilled person shows the RCD isn’t needed.
  • In India, RCDs are sold as RCCBs (or RCBOs), and are still often called ELCBs; the product standard is IS 12640. India’s National Electrical Code, SP 30:2023 (Part 3, Section 1), notes that the CEA safety regulations make a 30 mA RCD mandatory for installations of 1 kW and above. It recommends one for every home whatever its load, plus a 300 mA RCD at the point of supply to guard against fire from leakage currents.

Important

RCDs and GFCIs can’t tell when current flows through a person from live to neutral, because that current still returns on the neutral and the circuit stays balanced. They reduce shock risk; they don’t make live work safe.

RCD types

Modern electronics can produce leakage currents that aren’t pure AC. RCDs are classified by the waveforms they can detect:

  • Type AC: sinusoidal AC only. Since Amendment 2 of BS 7671 (2022), Type AC may only be used for fixed equipment known to produce no DC components.
  • Type A: AC plus pulsating DC, the usual choice for homes today.
  • Type F: Type A plus mixed frequencies, for equipment with single-phase variable-speed drives such as some washing machines and heat pumps.
  • Type B: all of the above plus smooth DC, needed for some three-phase inverters and EV chargers that lack built-in DC fault detection.

RCBOs: one device per circuit

An RCBO combines a breaker and an RCD in a single module. The benefit is selectivity: a leakage fault on one circuit trips only that circuit, instead of an RCD shared by several circuits switching off the lights, fridge and outlets together. That is why RCBO-based consumer units are now common in the UK. In North America, GFCI circuit breakers and dual-function AFCI/GFCI breakers do a similar job. (A “combination” AFCI is something else: an arc-fault breaker that detects both series and parallel arcs.)

AFCIs and AFDDs: protecting against fire

Damaged cords, crushed cables and loose terminals can create small electrical arcs. They may draw little current, so a breaker doesn’t notice, but they run hot enough to ignite nearby material.

Arc-fault devices analyze the current waveform for the signature of arcing and disconnect the circuit.

  • United States: the NEC requires AFCI protection for most 120 V, 15 A and 20 A branch circuits supplying living areas of homes, such as bedrooms, living rooms and kitchens. Exact locations depend on the code edition adopted locally.
  • UK: BS 7671 requires AFDDs on socket-outlet circuits rated up to 32 A in higher-risk residential buildings, houses in multiple occupation, purpose-built student accommodation and care homes, and recommends them elsewhere.

Note

The UK Wiring Regulations were updated again with Amendment 4 (2026), published in April 2026. Codes change: always check the edition and amendment in force for your project.

How to look after them

  • Press the test button as the manufacturer recommends. For GFCIs, that is commonly monthly. The device should trip immediately and reset.
  • Don’t keep resetting a device that keeps tripping. Unplug everything on the circuit, reset, then reconnect one item at a time. A persistent trip with nothing connected points to a wiring fault.
  • Outdoor trips after rain often mean moisture in an outdoor outlet or fitting.
  • Never bypass or remove a protective device. If it trips for no obvious reason, have a qualified electrician investigate.

For the other half of the safety system, read earthing, grounding and bonding explained.

Topics
  • Electrical safety
  • Home electrics
  • Standards & codes

Sources

  1. Mythbusters #8: socket-outlets must be protected by a 30 mA RCD (Regulation 411.3.3) (opens in a new tab) The IET, Wiring Matters
  2. Guide to ground-fault sensing (UL 943 trip-time curve) (opens in a new tab) IAEI Magazine
  3. Ground-Fault Circuit Interrupter (GFCI) Protection (opens in a new tab) IAEI Magazine
  4. 5 things you need to know about Amendment 2 to the 18th Edition (RCD types, AFDDs, 30 mA protection) (opens in a new tab) Electrium
  5. IET and BSI publish Amendment 4 (2026) to BS 7671:2018 (opens in a new tab) The IET
  6. NFPA 70, National Electrical Code (Articles 210 and 240) (opens in a new tab) NFPA
  7. SP 30:2023, National Electrical Code of India (Part 3/Sec 1, clause 5.5.3.10, residual current devices in homes) (opens in a new tab) Bureau of Indian Standards, via Public.Resource.Org
Free

Voltage Drop Calculator

VD = k × I × L × (R cos φ + X sin φ)

Single-phase, three-phase and DC voltage drop in sq mm or AWG under 15 national codes (IEC, NEC, BS 7671, SP 30 and more), with your own cable data if you have it.

Himanshu Amdavadi

Owner, iPower Switchgear · Power System Analysis & Design Consultancy

Himanshu Amdavadi is an electrical engineering professional and the owner of iPower Switchgear, an engineering consultancy based in Ahmedabad, Gujarat, India, specializing in power system analysis services and comprehensive electrical design consultancy.

With over 9 years of specialized industry experience across industrial power distribution, switchgear engineering, short-circuit calculations, and protection coordination, he provides engineering consultancy ensuring system reliability, safety, and compliance with IEC, IEEE, NEC, and Indian Standards (SP 30 / IS). As founder and technical editor of EngiLoop, he rigorously checks every calculation, formula, and technical guide before publication.

Core Engineering Expertise
Power System Analysis Electrical Design Consultancy Protection Coordination Switchgear Engineering Short-Circuit Calculations Industrial Standards (IEC / IS / NEC)